Transformers & Mutual Inductance - Physics 2

  1. What is the RMS current drawn from the primary source? (Use ω=2π(60)≈377 rad/s\omega = 2\pi(60) \approx 377 \text{ rad/s}, giving ωL≈10 Ω\omega L \approx 10 \ \Omega.)
    Answer: I1,rms≈8.49 AI_{1,\text{rms}} \approx 8.49 \text{ A}, because the secondary voltage is 240 V240 \text{ V} RMS, the secondary impedance is ∣Z2∣=(10)2+(10)2=102 Ω|Z_2| = \sqrt{(10)^2+(10)^2} = 10\sqrt{2} \ \Omega, giving I2≈16.97 AI_2 \approx 16.97 \text{ A}, and the correct transformer current relation I1N1=I2N2I_1 N_1 = I_2 N_2 gives I1=(N1/N2)I2=(1/2)(16.97)≈8.49 AI_1 = (N_1/N_2)I_2 = (1/2)(16.97) \approx 8.49 \text{ A}. Transformer problems test two key relationships: the voltage ratio and the current ratio. These are not the same ratio — they go in opposite directions. For a turns ratio N1:N2N_1 : N_2, voltage steps up by N2/N1N_2/N_1, while current steps down by the same factor (because an ideal transformer conserves power: V1I1=V2I2V_1 I_1 = V_2 I_2). Here's the correct approach. The secondary voltage is V2=V1⋅(N2/N1)=120×2=240 V RMSV_2 = V_1 \cdot (N_2/N_1) = 120 \times 2 = 240 \text{ V RMS}. The secondary load has R=10 ΩR = 10\ \Omega and XL=ωL≈10 ΩX_L = \omega L \approx 10\ \Omega, so ∣Z2∣=102+102=102 Ω|Z_2| = \sqrt{10^2 + 10^2} = 10\sqrt{2}\ \Omega. The secondary current is I2=240/(102)≈16.97 AI_2 = 240/(10\sqrt{2}) \approx 16.97 \text{ A}. Now apply the transformer current relation: I1N1=I2N2I_1 N_1 = I_2 N_2, which gives I1=I2⋅(N2/N1)⋅(N1/N1)I_1 = I_2 \cdot (N_2/N_1) \cdot (N_1/N_1)... more simply, I1=(N2/N1)⋅I2I_1 = (N_2/N_1) \cdot I_2 is wrong — the correct form is I1=(N2/N1)⋅I2I_1 = (N_2/N_1) \cdot I_2 reversed: I1=(1/2)(16.97)≈8.49 AI_1 = (1/2)(16.97) \approx 8.49 \text{ A}. This is answer D. Choice A incorrectly multiplies I2I_2 by 2 (the voltage ratio) instead of dividing — confusing the voltage and current ratios. Choice B claims current is unchanged in a step-up transformer, which violates power conservation entirely. Choice C correctly sets up the referred-impedance method but then computes I1=V1/ZrefI_1 = V_1/Z_\text{ref} and gets 33.9 A, which is actually the same error as A — it divided the impedance by 4 correctly, but 120/(102/4)=120×4/(102)=33.9120/(10\sqrt{2}/4) = 120 \times 4/(10\sqrt{2}) = 33.9 — an arithmetic inconsistency with its own stated logic. Remember: In a step-up transformer, primary current is larger than secondary current — the source supplies more current at lower voltage. Always use I1/I2=N2/N1I_1/I_2 = N_2/N_1, not the voltage ratio.
  2. A student claims that the mutual inductance MM computed using coil B as the 'primary' (flux from B linking A) must equal MM computed using solenoid A as the 'primary' (flux from A linking B), but also argues that the numerical computation is much harder when B is treated as the primary because coil B's field is non-uniform inside A. Which of the following best evaluates both aspects of this claim?
    Answer: Both aspects are correct: MAB=MBAM_{AB} = M_{BA} is guaranteed by the Neumann formula (a fundamental theorem), and computing MM with B as primary is indeed significantly harder because the short coil B produces a highly non-uniform field that does not uniformly link all turns of the long solenoid A. Whenever you encounter questions about mutual inductance, two key ideas should come to mind: the reciprocity theorem and the practical asymmetry of computation. The reciprocity theorem, derived from the Neumann formula, states that MAB=MBAM_{AB} = M_{BA} universally — it follows from the mathematical symmetry of the double line integral M=μ04π∮∮dℓ⃗A⋅dℓ⃗BrM = \frac{\mu_0}{4\pi} \oint \oint \frac{d\vec{\ell}_A \cdot d\vec{\ell}_B}{r}, which treats both coils identically. This is not a conditional result; it holds regardless of geometry, coil size, or turns count. So the student's first claim is rock solid. The second claim is equally valid. When solenoid A is the primary, its field inside is beautifully uniform: BA=μ0nAIAB_A = \mu_0 n_A I_A, so the flux through each turn of coil B is simply Φ=BA⋅A\Phi = B_A \cdot \mathcal{A}, giving M=μ0nANBA=(4π×10−7)(2000)(50)(5×10−4)≈6.28×10−5 HM = \mu_0 n_A N_B \mathcal{A} = (4\pi \times 10^{-7})(2000)(50)(5\times10^{-4}) \approx 6.28 \times 10^{-5} \text{ H}. Clean and simple. But if coil B is the primary, its short-coil field spreads non-uniformly over the entire length of solenoid A, requiring a complicated integral — much harder numerically. Both aspects of the student's claim are correct, making D the answer. A is wrong because it dismisses the computational difficulty — yes, the Neumann formula is symmetric in principle, but applying it numerically is far easier from one direction than the other. B is wrong because it incorrectly limits reciprocity to special media; the theorem is universal. C is wrong on both counts — reciprocity holds generally, and fewer turns does not make the non-uniform field integral simpler. Your study tip: always default to the long solenoid as primary when computing MM — uniform field means trivial flux calculation. Reciprocity then guarantees the answer applies both ways.
  3. What is the RMS power dissipated in the external load RLR_L, and how does it compare to the power dissipated in the secondary winding resistance r2r_2?
    Answer: Power in RLR_L is 92.16 W92.16 \text{ W} and power in r2r_2 is 23.04 W23.04 \text{ W}, so the load receives four times the power lost in the secondary winding resistance, consistent with the resistance ratio RL/r2=4R_L/r_2 = 4. When a transformer has a resistive secondary winding, you must treat the secondary circuit as a simple series loop: the induced secondary EMF drives current through both the winding resistance r2r_2 and the load RLR_L in series. Start by finding the secondary voltage using the turns ratio: V2=V1×N2N1=240×110=24 V RMSV_2 = V_1 \times \frac{N_2}{N_1} = 240 \times \frac{1}{10} = 24 \text{ V RMS}. This 24 V is the open-circuit secondary EMF — the voltage the ideal transformer delivers before internal losses. The secondary current is then I2=V2r2+RL=241+4=4.8 A RMSI_2 = \frac{V_2}{r_2 + R_L} = \frac{24}{1 + 4} = 4.8 \text{ A RMS}. Power in the load: PRL=I22⋅RL=(4.8)2×4=92.16 WP_{R_L} = I_2^2 \cdot R_L = (4.8)^2 \times 4 = 92.16 \text{ W}. Power lost in the winding: Pr2=I22⋅r2=(4.8)2×1=23.04 WP_{r_2} = I_2^2 \cdot r_2 = (4.8)^2 \times 1 = 23.04 \text{ W}. Since the same current flows through both, power divides proportionally to resistance, giving a 4:1 ratio — exactly RL/r2=4R_L / r_2 = 4. This confirms A is correct. B is wrong because "referring" r2r_2 to the primary is a circuit analysis technique for simplification — it doesn't mean r2r_2 physically stops dissipating power. The heat in r2r_2 is real regardless of which side of the circuit you model it on. C is wrong because r2≠RLr_2 \neq R_L; equal power would require equal resistances. The voltage doesn't split evenly here — it splits as 4.8 V vs. 19.2 V. D is wrong because winding resistance is purely ohmic; it does not create "core flux losses" or cause the primary to supply extra energy beyond what the secondary circuit actually consumes. Study tip: Whenever you see transformer problems with non-ideal windings, immediately redraw the secondary as a plain series circuit with V2V_2, r2r_2, and RLR_L — then apply Ohm's law and P=I2RP = I^2 R normally.
  4. Two ideal inductors with self-inductances L1=40 mHL_1 = 40 \text{ mH} and L2=90 mHL_2 = 90 \text{ mH} are wound on the same toroidal core such that all flux from one coil links the other. They are connected in series-aiding (fluxes add). Which of the following correctly gives the total inductance of the series combination and the mutual inductance MM?
    Answer: M=60 mHM = 60 \text{ mH} and Ltotal=250 mHL_{\text{total}} = 250 \text{ mH}, because for perfect coupling M=L1L2M = \sqrt{L_1 L_2} and series-aiding total inductance is L1+L2+2ML_1 + L_2 + 2M. When two inductors share a magnetic core with perfect coupling, two key formulas govern their behavior. First, the mutual inductance is M=kL1L2M = k\sqrt{L_1 L_2}, where kk is the coupling coefficient. "All flux links the other coil" means perfect coupling, so k=1k = 1, giving M=(40)(90)=3600=60 mHM = \sqrt{(40)(90)} = \sqrt{3600} = 60 \text{ mH}. Second, when inductors are connected series-aiding (currents enter the dotted terminals, so fluxes reinforce), the total inductance is Ltotal=L1+L2+2ML_{\text{total}} = L_1 + L_2 + 2M. The factor of 2 arises because mutual coupling adds voltage to both inductors simultaneously — inductor 1 sees extra EMF from inductor 2's changing current, and inductor 2 sees extra EMF from inductor 1's changing current. This gives Ltotal=40+90+2(60)=250 mHL_{\text{total}} = 40 + 90 + 2(60) = 250 \text{ mH}, confirming answer A is correct. Answer B gets MM right but uses L1+L2+ML_1 + L_2 + M — a classic error of counting only one mutual term. Mutual coupling is bilateral; both coils experience the effect, so you must count it twice. Answer C uses the wrong formula for MM, incorrectly averaging the self-inductances instead of taking their geometric mean, which inflates MM to 65 mH. Answer D correctly computes MM but then ignores the mutual terms entirely, as if the coils were magnetically isolated — the whole point of mutual inductance is that it changes the total. Remember the series-aiding formula as Ltotal=L1+L2+2ML_{\text{total}} = L_1 + L_2 + 2M (aiding adds, opposing subtracts) and M=kL1L2M = k\sqrt{L_1 L_2} for coupling — these two formulas together solve nearly every coupled-inductor problem.
  5. Two coils, 1 and 2, are placed near each other. The mutual inductance of the pair is M=50 mHM = 50 \text{ mH}. Coil 1 carries a current that varies as i1(t)=I0sin⁡(ωt)i_1(t) = I_0 \sin(\omega t) where I0=2 AI_0 = 2 \text{ A} and ω=100π rad/s\omega = 100\pi \text{ rad/s}. Coil 2 is open-circuited (no current flows in it). What is the peak magnitude of the EMF induced in coil 2, and what is the peak magnitude of the back-EMF induced in coil 1 due to mutual inductance with coil 2?
    Answer: Peak EMF in coil 2 is 10π V10\pi \text{ V}; peak back-EMF in coil 1 due to mutual coupling is zero, because coil 2 is open-circuited so i2=0i_2 = 0 for all time, meaning di2/dt=0di_2/dt = 0, and the mutually-induced EMF in coil 1 is −M di2/dt=0-M\,di_2/dt = 0. Mutual inductance questions require you to carefully track which coil's current is changing and apply the correct form of Faraday's law to each coil independently. The EMF induced in coil 2 by coil 1's changing current is E2=−Mdi1dt\mathcal{E}_2 = -M\frac{di_1}{dt}. Since i1=I0sin⁡(ωt)i_1 = I_0\sin(\omega t), we get di1dt=I0ωcos⁡(ωt)\frac{di_1}{dt} = I_0\omega\cos(\omega t), so the peak EMF in coil 2 is MI0ω=(0.050)(2)(100π)=10π VMI_0\omega = (0.050)(2)(100\pi) = 10\pi \text{ V}. Now, the back-EMF in coil 1 due to mutual coupling is E1,mutual=−Mdi2dt\mathcal{E}_{1,\text{mutual}} = -M\frac{di_2}{dt}. Because coil 2 is open-circuited, no current can flow: i2=0i_2 = 0 for all time, so di2/dt=0di_2/dt = 0, and this mutual back-EMF is exactly zero. Answer B captures both results correctly. Answer A is tempting because the reciprocity relation M12=M21M_{12} = M_{21} is real — but reciprocity tells you the same M governs both coils, not that both experience the same EMF regardless of current. The EMF in coil 1 depends on di2/dtdi_2/dt, not di1/dtdi_1/dt. Answer C incorrectly imagines the mutual EMF being "split" between the coils — there is no such sharing principle. Each coil gets its own Faraday expression. Answer D imports a transmission-line concept (open-circuit voltage doubling) into a lumped-circuit context where it simply doesn't apply; no such reflection mechanism exists here. Your strategy: always write out both mutual EMF equations, E2=−Mdi1dt\mathcal{E}_2 = -M\frac{di_1}{dt} and E1=−Mdi2dt\mathcal{E}_1 = -M\frac{di_2}{dt}, separately. Then substitute what you actually know about each current.
  6. What is the RMS current delivered to the load and the RMS current flowing through the common (shared) section of the winding (the lower 750 turns), and how does the current in the common section differ from the load current?
    Answer: Load current is 3.75 A3.75 \text{ A}, and the common section carries 0.9375 A0.9375 \text{ A}, because applying KCL at the tap node shows that the common section current equals the difference between the load current and the source input current: Icommon=IL−I1=3.75−2.8125=0.9375 AI_{\text{common}} = I_L - I_1 = 3.75 - 2.8125 = 0.9375 \text{ A}. Whenever you see an autotransformer problem, think of it as a KCL problem at the tap node — current doesn't just pass through; it splits and recombines in ways that differ from a conventional two-winding transformer. Start with the tap voltage. Since the winding is uniform, the voltage across the lower 750 turns is V2=200×7501000=150 VV_2 = 200 \times \frac{750}{1000} = 150 \text{ V}. The load current is then IL=V2RL=15040=3.75 AI_L = \frac{V_2}{R_L} = \frac{150}{40} = 3.75 \text{ A}. Now apply conservation of apparent power (ideal transformer) to find the source current: I1=V2V1IL=150200×3.75=2.8125 AI_1 = \frac{V_2}{V_1} I_L = \frac{150}{200} \times 3.75 = 2.8125 \text{ A}. At the tap node, KCL requires that the currents balance: the source delivers I1I_1 downward through the full winding, and the load draws ILI_L from the tap. The common (lower) section must carry the difference: Icommon=IL−I1=3.75−2.8125=0.9375 AI_{\text{common}} = I_L - I_1 = 3.75 - 2.8125 = 0.9375 \text{ A}. This is answer C. A is wrong because it ignores KCL entirely — in an autotransformer, source and load currents both flow through the common section but in opposite directions, so they partially cancel, not add. B correctly finds I1I_1 and ILI_L but then incorrectly assumes I1I_1 is what flows through the common section, confusing where the source current goes relative to the tap node. D inverts the turns ratio, applying it as a step-up when the tap clearly gives a lower fraction of the source voltage. The key study tip: always draw the tap node and write KCL explicitly — Icommon=IL−I1I_{\text{common}} = I_L - I_1 is the defining relationship of the shared winding section in a step-down autotransformer.
  7. By what factor does the fractional power loss (power lost in the line divided by total power transmitted) decrease when switching from scenario A to scenario B, and what turns ratio N1:N2N_1 : N_2 is needed at the step-up transformer if the generator produces 10 kV10 \text{ kV} RMS?
    Answer: The fractional power loss decreases by a factor of 100, and the required step-up turns ratio is N1:N2=1:10N_1:N_2 = 1:10, because increasing the voltage by a factor of 10 reduces the current by a factor of 10, and since Ploss∝I2P_{\text{loss}} \propto I^2, the loss decreases by a factor of 102=10010^2 = 100. Whenever you see a question about high-voltage power transmission, anchor your thinking to two key relationships: P=IVP = IV and Ploss=I2RP_{\text{loss}} = I^2 R. These two together reveal why voltage matters so much. For a fixed transmitted power PP, the current in the line is I=P/VI = P/V. In scenario A, IA=1 MW/10 kV=100 AI_A = 1\text{ MW}/10\text{ kV} = 100\text{ A}, giving a line loss of Ploss,A=(100)2×10=100 kWP_{\text{loss},A} = (100)^2 \times 10 = 100\text{ kW}, or a 10% fractional loss. In scenario B, IB=1 MW/100 kV=10 AI_B = 1\text{ MW}/100\text{ kV} = 10\text{ A}, so Ploss,B=(10)2×10=1 kWP_{\text{loss},B} = (10)^2 \times 10 = 1\text{ kW}, a 0.1% fractional loss. The ratio is 100 kW/1 kW=100100\text{ kW}/1\text{ kW} = 100. Because voltage increased by a factor of 10 and loss scales as I2∝1/V2I^2 \propto 1/V^2, the fractional loss drops by 102=10010^2 = 100. To step from 10 kV10\text{ kV} up to 100 kV100\text{ kV}, you need N1:N2=1:10N_1:N_2 = 1:10 — fewer primary turns than secondary turns. This confirms B is correct. Choice A gets the turns ratio right but claims only a factor-of-10 reduction, confusing I2RI^2R scaling with linear IRIR scaling. Choice C correctly identifies the factor-of-100 reduction but inverts the turns ratio — a step-*up* transformer needs more secondary turns, not more primary. Choice D makes both errors: it assumes loss is linear in current and inverts the transformer ratio. Study tip: Always remember the "double penalty" of low-voltage transmission — higher current hits you twice through I2RI^2R. When voltage increases by factor nn, power loss drops by n2n^2.
  8. A transformer manufacturer specifies a core material with relative permeability μr=5000\mu_r = 5000. An engineer proposes replacing it with a material of μr=2500\mu_r = 2500 while keeping all winding geometries identical. Assuming the transformer remains ideal (no core losses, complete flux linkage), which of the following correctly predicts the effect on the mutual inductance MM and the turns-ratio voltage relationship V2/V1=N2/N1V_2/V_1 = N_2/N_1?
    Answer: MM decreases by a factor of two because M∝μrM \propto \mu_r, but the turns-ratio voltage relationship V2/V1=N2/N1V_2/V_1 = N_2/N_1 remains valid because it follows from Faraday's law applied to a shared flux — the ratio N2dΦ/dtN_2 d\Phi/dt to N1dΦ/dtN_1 d\Phi/dt is independent of the absolute permeability as long as coupling is perfect. Transformer problems like this require you to separate two distinct questions: how does core permeability affect inductance values? and does the fundamental turns-ratio voltage law still hold? Keep those two questions independent in your mind. For a toroidal or ideal core geometry, mutual inductance scales as M=kL1L2M = k\sqrt{L_1 L_2}, where each self-inductance goes as L∝μrN2A/ℓL \propto \mu_r N^2 A / \ell. Since both L1L_1 and L2L_2 scale linearly with μr\mu_r, mutual inductance follows M∝μrM \propto \mu_r. Cutting μr\mu_r in half — from 5000 to 2500 — therefore cuts MM by exactly a factor of two. That confirms the first part of B. The turns-ratio voltage relationship V2/V1=N2/N1V_2/V_1 = N_2/N_1 comes directly from Faraday's law: V1=N1dΦdtV_1 = N_1 \frac{d\Phi}{dt} and V2=N2dΦdtV_2 = N_2 \frac{d\Phi}{dt}. When you divide them, dΦ/dtd\Phi/dt cancels completely. The ratio depends only on the winding turns, not on how large Φ\Phi actually is. So as long as coupling remains perfect (ideal transformer assumption), the voltage ratio is preserved regardless of permeability. B captures both truths correctly. A is wrong because it incorrectly claims the voltage ratio changes with μr\mu_r — the dΦ/dtd\Phi/dt cancellation disproves this. C is wrong because it denies that MM depends on permeability at all, ignoring that L∝μrL \propto \mu_r. D is wrong because it argues a quadratic dependence M∝μr2M \propto \mu_r^2; the "flux linking the secondary" is the same flux as produced by the primary — it doesn't scale with μr\mu_r a second time. Study tip: On transformer questions, always split your analysis — inductance magnitudes depend on core properties, but voltage ratios in an ideal transformer are purely geometric (turns counts). These are governed by different physics.
  9. Two ideal inductors with self-inductances L1=100 mHL_1 = 100 \text{ mH} and L2=400 mHL_2 = 400 \text{ mH} have mutual inductance M=100 mHM = 100 \text{ mH}. They are connected in series-opposing (fluxes partially cancel). A student calculates the coupling coefficient as k=M/L1L2=0.5k = M/\sqrt{L_1 L_2} = 0.5 and then claims that because k<1k < 1, the series-opposing total inductance must be positive (greater than zero). Is the student's conclusion correct, and what is the actual series-opposing total inductance?
    Answer: The conclusion is correct; the total inductance is Lopp=L1+L2−2M=300 mHL_{\text{opp}} = L_1 + L_2 - 2M = 300 \text{ mH}, which is indeed positive, consistent with k=0.5<1k = 0.5 < 1 preventing complete cancellation of the self-inductance terms. When two inductors are connected in series, the total inductance depends on whether their magnetic fluxes aid or oppose each other. For series-aiding, you add the mutual terms: Laid=L1+L2+2ML_{\text{aid}} = L_1 + L_2 + 2M. For series-opposing, both mutual terms subtract: Lopp=L1+L2−2ML_{\text{opp}} = L_1 + L_2 - 2M. The factor of 2 appears because each inductor's flux cuts through the other — there are two cross-coupling contributions, both reversed in the opposing case. Plugging in the given values: Lopp=100+400−2(100)=300 mHL_{\text{opp}} = 100 + 400 - 2(100) = 300 \text{ mH}. This is positive, and the student's conclusion (that it must be positive) happens to be correct — but for the right reason. The coupling coefficient k=M/L1L2=100/100×400=0.5k = M/\sqrt{L_1 L_2} = 100/\sqrt{100 \times 400} = 0.5 guarantees 2M<2L1L22M < 2\sqrt{L_1 L_2}, and by the AM-GM inequality, L1+L2≥2L1L2>2ML_1 + L_2 \geq 2\sqrt{L_1 L_2} > 2M, so the result is always non-negative when k≤1k \leq 1. This confirms C is correct. A is wrong because it invents a formula using ∣L1−L2∣|L_1 - L_2| that has no basis in circuit theory — you always sum both self-inductances, never subtract them from each other. B is wrong because it uses only a single mutual term (−M-M) instead of −2M-2M. Both cross-coupling interactions reverse sign in the opposing configuration, not just one. D is a tempting distractor — it gets the arithmetic right (300 mH) but falsely claims k<1k < 1 doesn't guarantee a positive result. In fact, it mathematically does, for any passive inductor pair. Study tip: Always remember the 2M2M factor in series inductor formulas — dropping one of the mutual terms is the most common error on coupled-inductor problems.
  10. If the AC source frequency is doubled while keeping the peak voltage V0V_0 constant, which of the following correctly describes what happens to the secondary RMS current and the power delivered to the load?
    Answer: The secondary RMS current remains unchanged and the power delivered to the load remains unchanged, because for an ideal transformer neither quantity depends on frequency — only on the turns ratio and applied voltage. The flux amplitude adjusts inversely with frequency so that the product ωΦ0\omega \Phi_0 remains constant. Whenever you see a transformer question involving frequency changes, anchor yourself to one key equation: the transformer turns ratio V2V1=N2N1\frac{V_2}{V_1} = \frac{N_2}{N_1}. For an ideal transformer, this relationship depends only on the turns ratio — not on frequency. Here's the deeper physics: the primary voltage is fixed at V0=1000 VV_0 = 1000\text{ V}, so the secondary voltage is always V2=V1⋅N2N1=1000⋅100500=200 VV_2 = V_1 \cdot \frac{N_2}{N_1} = 1000 \cdot \frac{100}{500} = 200\text{ V}, regardless of frequency. What actually adjusts internally is the flux amplitude Φ0\Phi_0: since V1=N1ωΦ0V_1 = N_1 \omega \Phi_0, doubling ω\omega cuts Φ0\Phi_0 in half, keeping the product ωΦ0\omega \Phi_0 — and therefore the induced voltage — constant. With V2V_2 unchanged, the secondary RMS current I2=V2,rmsRI_2 = \frac{V_{2,\text{rms}}}{R} stays the same, and so does the power P=V2,rms2RP = \frac{V_{2,\text{rms}}^2}{R}. Answer A is correct. Answer B misunderstands what "rate of change of flux" means in this context. Doubling frequency also halves flux amplitude, so the EMF — which depends on ωΦ0\omega \Phi_0 — doesn't change. Answer C describes behavior relevant to a real transformer with significant primary inductance, but for an ideal transformer, there is no meaningful "magnetizing current" limiting flux linkage — the primary voltage fully determines the secondary voltage. Answer D confuses energy-per-cycle with power; if each cycle delivers the same energy but you have twice as many cycles, total power is unchanged because energy-per-cycle is halved when voltage is constant. Your takeaway: for ideal transformers, frequency is irrelevant — only the turns ratio and applied voltage matter. When frequency changes, flux amplitude compensates silently.

Start this quiz